Vaisala HMD/W 40 and 50 RH and Temperature Transmitter
|
| |
|
Quantity in Basket:
None
Code: VIHMDW4050
Price: $170.00
Shipping Weight: 2.00 pounds
|
| |
Vaisala HMD/W40/50 Humidity and TemperatureTransmitters
|
Ideal for indoor air conditioning systems. Features excellent stability, easy installation and reliable operation. Interchangeable sensor, no recalibration required. |
- Specially designed for building energy management systems
- 10 ... 90 % RH measurement
- -10 ... +60 °C (+14 ... +140 °F) operating range for duct units
- -5 ... +55 °C (+23 ... +131 °F) operating range for wall units
- 4 ... 20 mA 2-wire output (HMD/W40)
- Selectable voltage 3 wire output (HMD/W50)
- Combines excellent stability with easy installation and reliable operation
- No recalibration needed
- Fully interchangeable Vaisala INTERCAP ® Sensor is easy to replace
- Low cost
|
| 40 Series: 2-wire, 4 to 20 mA output |
| Wall Mount |
RH only |
HMW40U |
| |
RH & T |
HMW40Y |
| Duct Mount |
RH only |
HMD40U |
| |
RH & T |
HMD40Y |
|
| 50 Series: 3-wire, variable voltage output |
| Wall Mount |
RH only |
HMW50U |
|
RH & T |
HMW50Y |
| Duct Mount |
RH only |
HMD50U |
|
RH & T |
HMD50Y |
|
|
| |
Relative humidity measurement |
| |
Measurement range
Accuracy at +20 °C (+68 °F)
Operating range:
HMD40/50
HMW40/50
Sensor |
10 ... 90 % RH
better than ± 3 % RH
0 ... 100 % RH
0 ... 90 % RH
Vaisala INTERCAP ® |
Temperature measurement |
| |
Measurement range
HMD40/50
HMW40/50
Accuracy at +25 °C
Sensor |
-10 ... +60 °C (+14 ... +140 °F)
-5 ... +55 °C (+23 ... +131 °F)
± 0.3 °C (± 0.54 °F)
Pt 1000 IEC 751 class B
|
Operating environment |
| |
Operating temperature
HMD40/50
HMW40/50
Storage temperature |
-10 ... +60 °C (+14 ... +140 °F)
-5 ... +55 °C (+23 ... +131 °F)
-40 ... +60 °C (-40 ... +140 °F)
|
Inputs and outputs |
| |
Operating voltage
HMD/W40
HMD/W50 for
0 ... 1 V output
0 ... 10 V output
Power consumption
HMD/W40
HMD/W50 |
10 ... 28 VDC
12 ... 35 VDC/ 12 ... 24 VAC
15 ... 35 VDC/ 15 ... 24 VAC
min. 4 mA
6 mA (typical)
|
Mechanics |
|
Material (housing)
Housing classification (HMD40/50) |
ABS plastic
IP65 (NEMA 4) |
|
|
| |