| SPECIFICATIONS |
| Maximum Pressure: |
4" w.c. and less = 2 PSI; 5" w.c. and above = 10 PSI |
| Media compatibility: |
Air and compatible non combustible, non corrosive gasses |
| Accuracy: |
Axxx0-xx - 1.00%; Axxx1-xx - 0.50% |
Temperature Ranges (Compensated and Operating):
|
-10° to 140°F (-23° to 60°C) |
| Thermal Effect*: |
+/- 0.012% FS/°F |
| Output Signal: |
4-20 mA (option) |
| Loop Resistance: |
750 Max (for internally sourced power)
1800 Max (for externally sourced power of 36 VDC) |
| Power Supply: |
Universal 16-265 VAC or VDC |
| Housing Material: |
Glass Filled Nylon |
| Enclosure Rating: |
Designed to meet NEMA 4X face; with optional
cover the entire product is weatherproof |
| Electrical Connections: |
screw terminals |
| Response Time: |
<100 ms |
| Display: |
A1 - 4 Digit, red LED, ½" digits |
| |
A2 - 4 Digit, red LED, ½" digits ; Process Arch |
| |
A3 - 4 Digit, red LED, ½" digits ; Process Arch ; LCD programming display |
| |
A4 - 4 Digit, red LED, ½" digits ; Process Arch ;OLCD programming display |
| Relays on Series A3 and A4: |
(2) SPDT 8 Amps @ 250 VAC, 5A @30 VDC |
| Process Connection: |
Push on connection for 3/16" tubing |
| Agency Approvals: |
Pending - UL, C-UL, CE |
| *Custom calibration including improved accuracy and thermal effect are available. |